Instability Analysis of Grid-Connected Inverters During Low-voltage-ride Through Process
                  Conference: PCIM Asia 2024 - International Exhibition and Conference for Power Electronics, Intelligent Motion, Renewable Energy and Energy Management
                  08/28/2024 - 08/30/2024 at Shenzhen, China              
doi:10.30420/566414094
Proceedings: PCIM Asia 2024
Pages: 6Language: englishTyp: PDF
            Authors:
                          Yang, Qijin; Liu, Yuanda; Han, Yong; Zou, Chunbao; Luo, Cheng
                      
              Abstract:
              During the low voltage ride-through (LVRT) process, it is found that grid-connected inverters may experience instability. The reason is that when outputting the reactive current according to the grid-voltage dip value, the large grid impedance may lead to the root of the characteristic expression moving outside the unit circle. A low-pass filter (LPF) with a designed cut-off frequency is proposed to be used with the voltage magnitude detection module. It is revealed that LPF will expand the variation range of grid impedance and enhance the stability of the system. The simulation results have verified the correctness of the theoretical analysis.            

