Traction systems according to DIN EN 50163 and networks of the electrical power supply differ significantly in the limits of the non-permanent voltages, so that the normal threshold voltage of 78 % of the nominal voltage (DIN EN 61243-1 (VDE 0682-411):2010-09) is not applicable to traction systems. This corrigendum modifies the threshold voltage to 70 % of the nominal voltage (applying part 4.2.1.2.1 and part 6.2.1.3).