Experiences with on-site dielectric testing during commissioning tests of world’s first offshore HVDC GIS ±320 kV

Konferenz: VDE Hochspannungstechnik - 4. ETG-Fachtagung
08.11.2022 - 10.11.2022 in Berlin, Germany

Tagungsband: ETG-Fb. 169: VDE Hochspannungstechnik 2022

Seiten: 6Sprache: EnglischTyp: PDF

Autoren:
Kosse, Maria; Klein, Christoph; Claus, Matthias (Siemens Energy AG, Erlangen, Germany)
Tuczek, Maximilian (TenneT TSO GmbH, Bayreuth, Germany)

Inhalt:
Compact gas-insulated metal-enclosed systems for HVDC applications (HVDC GIS) have been developed for HVDC projects in need of space-saving installations, such as offshore platforms, cable transition stations or multi-terminal switching stations. HVDC GIS are on the market up to rated DC voltages of ±550 kV. Within the German offshore grid connection system DolWin6, the world’s first offshore HVDC GIS was successfully installed and tested during commissioning in the dockyard in year 2021. High-voltage testing was carried out with AC voltage stress and partial discharge measurement according to recommendations within CIGRE technical brochure 842. As a special part of the commissioning, also a high-voltage test using DC voltage was performed. All commissioning tests of the offshore HVDC GIS ±320 kV were passed successfully.